9
|
Configuration
Installer reference guide
134
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
#
Code
Description
[A.6.5]
[2‑0B]
Ext amb. sensor offset
: Offset on the
ambient temperature sensor measured on the
external outdoor temperature sensor.
–5°C~5°C, step: 0.5°C
Disable protections
The software is equipped with an "installer-on-site" mode ([A.6.D]:
Disable
protections
) that disables automatic operation by the unit.
#
Code
Description
[A.6.D]
N/A
▪
ON: Automatic operation is disabled. All
protective functions are disabled. If the user
interface home pages are off, the unit will NOT
operate automatically. To enable automatic
operation and the protective functions, set
Disable protections=OFF.
▪
OFF: 12 hours after the first power-on, the unit
will automatically set Disable protections=OFF,
ending "installer-on-site" mode and enabling
the protective functions. If the installer returns
to the site, the installer has to set Disable
protections=ON manually.
Pump operation
When the pump operation function is disabled the pump will stop if the outdoor
temperature is higher than the value set by [4‑02] or if the outdoor temperature
drops below the value set by [F‑01]. When the pump operation is enabled, the
pump operation is possible at all outdoor temperatures.
#
Code
Description
N/A
[F‑00]
Pump operation:
▪
0: Disabled if outdoor temperature is higher
than [4‑02] or lower than [F‑01] depending on
heating operation mode.
▪
1: Possible at all outdoor temperatures.
Pump speed limitation
Pump speed limitation main zone [9‑0E] and pump speed limitation additional zone
[9‑0D] define the maximum pump speed. In normal conditions, the default setting
should NOT be modified. The pump speed limitation will be overruled when the
flow rate is in the range of the minimum flow (error 7H).
Summary of Contents for ERLA03DAV3
Page 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Page 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...