Configuration
Installer reference guide
109
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
Leaving water temperature: Additional zone
#
Code
Description
[A.3.1.2.1]
N/A
Select the setpoint mode of the leaving water
temperature.
LWT setpoint mode
:
▪
0 (
Fixed
): Absolute
▪
1 (
Weather dep.
): Weather-dependent
▪
2
(
Fixed/scheduled
):
Absolute
+
scheduled (only if
Unit
control
method
=
LWT control
)
▪
3 (
WD/scheduled
): Weather-dependent +
scheduled (only if
Unit
control
method
=
LWT control
)
[7.7.2.1]
[0-00]
[0-01]
[0-02]
[0-03]
If you selected weather-dependent curve as a
setpoint mode, adjust the curve to your needs.
(a)
Set weather-dependent heating
:
[0-00]
[0-01]
Ta
Tt
[0-03]
[0-02]
▪
T
t
: Target leaving water temperature
(additional)
▪
T
a
: Outdoor temperature
(a)
Leaving water temperature: Delta T source
The Delta T is the required temperature difference between entering and leaving
water. This applies to both temperature zones. Change the value of Delta T if
another minimum temperature difference is required for the good operation of the
heat emitters in heating mode.
#
Code
Description
[A.3.1.3.1]
[1-0B]
Delta T for heating
Range: 3°C~10°C
Leaving water temperature: Modulation
To allow better matching of the heat pump capacity with the actual required
capacity, enable the leaving water temperature modulation. If modulation is
enabled, the unit calculates the leaving water temperature according to the
difference between desired and actual room temperature. As a result, the
heat pump will have less start/stop cycles and thus operate more economical.
If modulation is enabled, you can also set the maximum modulation of the leaving
water temperature. The maximum modulation is the value by which the desired
leaving water temperature is increased or lowered.
Summary of Contents for ERLA03DAV3
Page 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Page 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...