9
|
Configuration
Installer reference guide
102
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
B
A
C
b
c
a
A
Additional zone leaving water temperature zone
B
Room 1
C
Room 2
a
User interface is located at the unit
b
User interface is located in the room
c
Remote controller of the heat pump convector
At unit
:
The other user interface:
▪
is automatically set to
In room
,
▪
acts as room thermostat if
RT control
is selected.
In room
:
This user interface acts as room thermostat if
RT control
is selected.
The other user interface is set to
At unit
.
Space heating: Number of LWT zones
#
Code
Description
N/A
[7-02]
Number of LWT zones
▪
0 (
1 LWT zone
)
▪
1 (
2 LWT zones
)
The system can supply leaving water to up to 2 water temperature zones. During
configuration, the number of water zones must be set.
1 LWT zone
:
There is only 1 leaving water temperature zone. This zone is called the main leaving
water temperature zone.
a
a
Main LWT zone
2 LWT zones
: