9
Mixer module
Operating Instructions
51
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
9
Mixer module
In addition to the direct HC, the emitter type can be extended by ad-
ditional HCs using mixer modules EHS157068. These additional
HCs can be configured independently of the direct HC. The configur-
ation is similar to the configuration of the direct HC (see
Only a limited selection of parameters and functions is available (see
The optional EHS157068 mixer module does not have its own con-
trol unit. For configuration and operation, it must be connected to the
RoCon+ controller installed in the heat generator or to a EHS157034
room station via a CAN bus line. The mixer module can be operated
in terminal mode from both operating units (see
).
A unique device ID (≥ 1) must be set on the address switch of the
mixer module (see
) for the HC to be controlled by this mixer
module, which must be synchronised with the [Heating circuit as-
signment] parameter of the mixer module (see
Fig. 9-1
Setting the device ID for the EHS157068 mixer module
The current operating status can be determined directly on the
EHS157068 mixer module (see
).
Fig. 9-2
Explanation of symbols for EHS157068 status displays
Item
LED
Description
1
Red
Flashing: Internal error
(The error code is communicated to the relevant con-
trol unit via the CAN bus)
To: Undervoltage of the internal clock after a power
failure (>10 h)
2
Gree
n
To: Display during operation, mixer module switched
on
3
Gree
n
To: CAN communication
4
Gree
n
To: Mixer circuit pump switched on
5
Gree
n
To: Mixer valve "Open" is activated
6
Gree
n
To: Mixer valve "Closed" is activated
Tab. 9-1
9.1
Mixer module start screen
(terminal function)
Fig. 9-3
Mixer module start screen
The start screen for the mixer module (
of the RoCon+ HP start screen. The meaning of the icons is the
same
, but the mixer temperature is the only system temper-
ature displayed (
The start screen for the mixer module is displayed in the menu
[→ Main menu → Terminal → Mixer #X]. Briefly pressing the rotary
switch switches to the mixer menu. A long press of the rotary switch
switches to the menu of the local control panel.
9.2
Mixer valve parameter overview
Menu: Operating mode
see
Menu: User
Room temperature setpoint 1
Room temperature setpoint 2
Room temperature setpoint 3
Room
Reduce
Reduce
Room temperature reduced
Room temperature absent
Fig. 9-4
Parameter in menu: "User"
Menu: Time program
Party
Away
Vacation
Holiday
HC auto 1
Heating circuit auto. 1
HC auto 2
Heating circuit auto. 2
Fig. 9-5
Parameter in menu: "Time program"