7
Parameter settings
Operating Instructions
48
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
7.10
Statistics
[→ Main menu → Statistics]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE HF
Ext. energy
source, hot
water
-
The volume of heat of the additional heat generator for domestic hot water
preparation in kWh is displayed.
-
kWh
S
S
Ext. energy
source, heat-
ing
-
The volume of heat of the additional heat generator for heating mode in
kWh is displayed.
-
kWh
S
S
Energy HP,
cooling
-
The volume of heat of the heat pump for cooling mode in kWh is displayed.
-
kWh
S
S
Energy HP,
heating
-
The quantity of heat in the heat pump for heating is displayed in kWh.
-
kWh
S
S
Energy, hot
water
-
The quantity of heat for domestic hot water preparation is displayed in
kWh.
-
kWh
Energy con-
sumed
-
The total volume of heat of the heat pump in kWh is displayed.
-
kWh
Runtime,
compressor
-
The running time of the refrigerant compressor in h is displayed.
-
1 h
S
S
Runtime,
pump
-
The runtime of the internal heating circulation pump is displayed in h.
-
1 h
S
S
Reset
-
All parameters listed in the Statistics menu are reset to "0". (Specialist code
required).
-
-
Tab. 7-33
Parameter in menu: "Statistics"
INFORMATION
Depending on the device type, the system configuration
and the status of the device software, individual listed in-
formation parameters cannot be displayed or can be dis-
played at a different parameter level.
7.11
Configuration wizard
Only after hardware reset.
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE HF
Direct circuit
configuration
0 – 15
Setting of the heating circuit ID for the direct heating circuit of the Daikin
Altherma EHS(X/H). The HC ID must be unique throughout the RoCon sys-
tem. There must be no overlap with the HC IDs of optional mixer circuits.
0
1
N
E
Bus ID heat
generator
0 – 7
The setting may only be changed if more than 1 heat generator is integ-
rated in the RoCon system. Several heat generators integrated in the heat-
ing system must be regarded as a special application. If necessary, contact
a service technician.
0
1
N
E
Time master
No
Activation of a system-wide time master. The Time Master synchronises all
controllers in the RoCon system with the time and date set on the Time
Master. For all other control panels in the system, it is no longer possible to
enter the time and date. There must only be one time master in the entire
system. The parameter is not available if the Time Master parameter is ac-
tivated on another controller in the RoCon system.
-
N
E
Yes
Tab. 7-35
Parameters in menu: "Configuration Wizard"