7
Parameter settings
Operating Instructions
38
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
7.5.5
Menu: Intelligent Storage Mgmt
[→ Main menu → Settings → ISM]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE HF
Continuous
heating
This function enables uninterrupted heating, even when the evaporator is
being defrosted. This enables high comfort to be guaranteed, even with
rapidly reacting heating systems (e.g. convectors).
-
N
E
Off
No uninterrupted heating
On
Uninterrupted heating. When the evaporator is being defrosted, heat for
heating is taken from the storage tank.
Heating sup-
port (HZU)
Heating support from hot water storage tank if minimum temperature is ex-
ceeded (see
and [HZU hysteresis] parameter).
-
N
E
Off
No heating support
On
Heating support function active
Heating sup-
port power
3 - 40 kW
The setting limits the heating support output.
15 kW
1 kW
N
E
HZU hyster-
esis
2 - 15
Only if [Heating support (HZU)] parameter = On.
Heating support is activated if
Tdhw > T 4 K and Tdhw > [Feed temperature setpoint] + 1 K.
Heating support is deactivated if
Tdhw < THZUmin or Tdhw < [Feed temperature setpoint].
THZUmin = currently active hot water target temperature [Feed temperat-
ure setpoint] + set [HZU hysteresis] parameter value.
Tdhw = current hot water storage tank temperature
[Feed temperature setpoint] = currently active feed target temperature (see
5
1
N
E
HZU max.
temperature
5 - 85 °C
The setting limits the feed target temperature (measured against t
V
, BH)
when the heating support function is active.
60 °C
1 °C
N
E
Min. pump
power
40 - 80%
Lower limit for pump operation. Only used when heating support is active
or heat is generated by an external heat source.
50%
1%
N
E
Max. pump
power
60 - 80%
Upper limit for pump operation. Only used when heating support is active
or heat is generated by an external heat source.
80%
1%
N
E
Tab. 7-17
Parameter in menu: "Intelligent Storage Mgmt"
7.5.6
Menu: Special functions
[→ Main menu → Settings → Special]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE HF
Quiet mode
Mode for quiet operation at reduced output (see
).
-
N
E
Inactive
Inactive
Active
Active
Active at night
Only operated in whisper mode at night from 22:00 to 6:00 hours.
Noise level
If low-noise operation is selected, three noise levels can be set.
-
N
E
Min. noise reduc-
tion
The output can fall in colder ambient conditions.
Med. noise reduc-
tion
Reduced output is possible under all conditions.
Max. noise reduc-
tion
The output is reduced under all conditions.
Tab. 7-18
Parameter in menu: "Special functions"