7
Parameter settings
Operating Instructions
36
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Interlink func-
tion
Configuration for systems that are operated with 2 different feed target
temperatures (see
).
One possible application is, for example, the additional integration of an
HP convector in a surface heating and cooling system.
Prerequisite: 2 room thermostats are connected to Daikin Altherma EHS(X/
H) plug connection J16.
-
N
E
Off
Deactivated
On
Evaluation of the heating and cooling switching contacts at plug connec-
tion J16 on the PCB of RoCon BM2C.
Activation of cooling mode only by switching the operating mode to "Cool-
ing" (see
Setting of the [Room thermostat] parameter is no longer evaluated.
▪ Open switching contacts: Only frost protection active
▪ "Heating" and "Automatic 1" / "Automatic 2" operating mode active dur-
ing the switching cycles in day mode.
▪ Closed heating switching contact = IL1:
▪ It is regulated to the normal feed target temperature in accordance
with the parameter settings in [→ Main menu → Configuration
→ Heating].
▪ Closed cooling switching contact = IL2:
▪ The system is regulated to the increased feed target temperature
(normal feed target tempe value of the [Interlink temperature
rise] parameter. Priority if both switching contacts are closed!
▪ "Cooling" operating mode active.
▪ Closed heating switching contact = IL1:
▪ It is regulated to the normal feed target temperature in accordance
with the parameter settings in [→ Main menu → Configuration
→ Heating].
▪ Closed cooling switching contact = IL2:
The system is regulated to the reduced feed target temperature (normal
feed target temperature value of the [Interlink temperature reduction] para-
meter. Priority if both switching contacts are closed
Program-
mable output
(230V)
Configuration of the multi-function output (230 V, J14 connection):
-
N
E
Inactive
The output has no function.
Heating circuit re-
quest
Header pump – The output becomes active as soon as a system heating
circuit reports a heat requirement to the heat generator.
Circulation request Circulation pump – The output is activated either after the time program of
the circulation pump or after the time program of the domestic hot water
preparation, depending on the parametrisation (see
Direct heating cir-
cuit request
Feeder pump – The output becomes active as soon as a heat requirement
is pending for the direct heating circuit of the heat generator.
Func. burner
blocking con-
tact
Resistance values Selection of the functionality of the EXT switching contact (J8) (see
)
-
N
E
Burner blocking
contact