Parameter settings
Operating Instructions
44
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE HF
Circulation
pump control
Setting of the interval control for an optional circulation pump. Use in
France not permitted!
Off
1 min
E
E
Off
Deactivated.The circulation pump runs permanently during the release
times of the assigned switching time program ([Circulation pump control]
parameter).
1 - 15 min
The circulation pump runs clocked (clock cycle ratio: pump runtime = set-
ting value each 15 min).
Thermal disin-
fection day
Setting of the day for thermal disinfection of the hot water storage tank.
Off
-
E
E
Off
No thermal disinfection
Monday
...
Sunday
Day of thermal disinfection
Daily
Daily thermal disinfection
Thermal disin-
fection start
time
00:00 - 23:45
Setting of the start time for thermal disinfection of the hot water storage
tank (format hh:mm).
03:30
15 min
N
E
Thermal disin-
fection temp.
60 – 70 °C
Setting of the hot water target temperature during thermal disinfection of
the hot water storage tank.
65 °C
1 °C
N
E
Tab. 7-24
Parameter in menu: "Hot water"
7.6.6
Menu: Additional programs
[→ Main menu → Configuration → Addition]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE HF
Relay Test
Manual control of individual relays for test purposes. After confirmation of
this parameter with the rotary button, the list of relays 1 - 9 is displayed with
a checkbox on the display. For selection and confirmation of a relay with
the rotary button, a tick is placed in the checkbox and the respective relay
is activated. Multiple selection is possible.
-
-
N
E
Output J1
Output J1 (internal heating circulation pump), output pump
Output J14
Output J14 (circulation pump), mixer "Open"
Output J2 contact
A
Contact A on output J2 (3UVB1 switching valve), mixer "Closed"
Output J2 contact
B
Contact B on output J2 (3UVB1 switching valve)
Output J12 3UV
DHW open
Output J12, 3UV DHW switching valve "Closed"
Output J12 3UV
DHW closed
Output J12, 3UV DHW switching valve "Open"
Connection J3 N/
O contact B
Connection J3 (potential-free relay: normally open B-B1) - AUX
Connec. J3
changeover con-
tact A
Connection J3 (potential-free relay: Changer A-A1/A-A2) - AUX
Output J10
Output J10 (A1P power supply)
Output J17 relay
K2
Output J17 (pin 3) - relay K2 (RTX-EHS) output XBUH1 T2
Output J17 relay
K1
Output J17 (pin 2) - relay K1 (RTX-EHS) output XBUH1 T3
Output J17 relay
K3
Output J17 (pin 4) - relay K3 (RTX-EHS) output XBUH1 T1
Air Purge
Activation of automatic ventilation of the Daikin Altherma EHS(X/H) and the
connected HC.
-
N
E
Off
Deactivated
On
Start of the ventilation function