Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE HF
Screed
Function for screed drying
-
N
E
Off
Deactivated
On
The feed target temperature is regulated according to the set [Screed pro-
gram]. The day on which the screed function is activated is not included in
the running time of the screed program. The first day starts when the day
changes at 00:00 am. On the day of activation, heating is carried out for the
remaining time with the feed target temperature of the program of the first
day (see
).
Screed Pro-
gram
10 - 70 °C per
heating day
Setting of the sequence program of the screed heating. An individual feed
target temperature can be set for each day for a maximum duration of 28
days. The end of the screed program is defined by the 1st day with the tar-
get value setting "Off" (see
).
See
1 °C
N
E
Tab. 7-25
Parameter in menu: "Additional programs"
7.7
Information
[→ Main menu → Information]
7.7.1
Overview
[→ Main menu → Information → Overview]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Mode
No request
Current mode of the heating pump.
-
-
S
S
Heating
Cooling
Domestic hot wa-
ter preparation
Defrost
Ext
External request:
-
-
S
S
No external mode Heat pump operates in normal operation.
Low rate
EVU function HT/NT active and low rate.
High rate
EVU function HT/NT active and high rate.
SGN
EVU function Smart grid active, normal operation.
SG1
EVU function Smart grid active, discharge: No heat pump operation, no
frost protection function.
SG2
EVU function Smart grid active, switch-on recommendation, operation at
higher target temperatures, inexpensive electricity.
SG3
EVU function Smart grid active, switch-on command and storage tank
charging to 70 °C, inexpensive electricity
RT
Room thermostat/Interlink:
-
-
S
S
Off
If [Interlink function] = On: frost protection only; otherwise: Off
Request
If [Room thermostat] = Yes
No heat request
If [Room thermostat] = Yes
IL1
If [Interlink function] = On: Normal feed target temperature
IL2
If [Interlink function] = On: In heating mode increased feed target temperat-
ure, in cooling mode reduced feed target temperature
Pump
Off
Status of the internal heating circulation pump (On/Off)
-
-
S
S
On
V
-
Current volume flow in the heating system
-
-
S
S
EHS
-
Current output of the optional backup heater in kW
-
-
S
S
TV
-
Current feed temperature after the plate heat exchanger (tV) in °C
-
-
S
S
TVBH
-
Current feed temperature after heating support (tV, BH) in °C
-
-
S
S
TR
-
Current return flow temperature in °C
-
-
S
S
Tdhw
-
Current temperature in hot water tank in °C
-
-
S
S
Psyst
-
Current water pressure in the heating network in bar
-
-
S
S