7
Parameter settings
Operating Instructions
34
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
7.5.3
Menu: External heat source
[→ Main menu → Settings → Ext. source]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE HF
Config. of ex-
ternal heat
source
Setting of whether there is an additional external heat generator for do-
mestic hot water preparation (DHW) and/or heating support (HZU).
-
N
E
No external heat
generator
The heat pump is the only heat source
Backup heater
BUH
Optional heating rod (3N~) installed in the storage tank
DHW + heating
support
An alternative heat generator (e.g. backup heater 1N~) provides domestic
hot water preparation and backup heating
Two external heat
generators
Two external heat generators: Alternative WEZ 1 (e.g. backup heater 1N~)
takes over domestic hot water preparation and alternative WEZ 2 takes
over heating support
Ext. hot water
power
1 - 40 kW
Heat output of the electric heater booster for domestic hot water prepara-
tion
3 kW
1 kW
N
E
Ext. power
level 1 (*)
1 - 40 kW
Heat output of the electric heater booster for heating support stage 1
See operating instructions for the BUxx heating element.
3 kW
1 kW
N
E
Ext. power
level 2 (*)
1 - 40 kW
Heat output of the electric heater booster for heating support stage 2
See operating instructions for the BUxx heating element.
3 kW
1 kW
N
E
Equilibrium
function (*)
The bivalence function is only relevant to operation of the optional heater
booster due to a backup request (room heating mode).
-
N
E
Aux. heating al-
ways possible
Operation of the backup heater is always possible.
Aux. heating T-biv.
dependent
Backup heater is only released if the temperature set in the [Equilibrium
Temp] parameter is undercut.
Equilibrium
Temp
-15 °C - +35 °C
Setting influences the effect of the potential-free AUX switching contact
(toggle switch output A) defined in the [AUX switching function] parameter.
Only if [Equilibrium function] parameter = heating up T-bivalence:
Outside temperature as of which the optional heater booster is activated to
support room heating. The bivalence temperature is relevant to operation
of the optional heater booster due to a backup request (room heating
mode). The temperature of the temperature sensor (information value Tem-
perature
A
) integrated in the heat pump outdoor unit is used for this.
0 °C
1 °C
N
E
Tab. 7-15
Parameter in menu: "External heat source"