7
Parameter settings
Operating Instructions
40
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
7.6.2
Menu: Heating circuit config.
[→ Main menu → Configuration → HC config]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE HF
Weather-de-
pendent
Selection of the method for determining the target feed temperature.
-
N
E
Feed temperature,
fixed
Feed temperature, fixed: Control to a fixed flow value (depending on oper-
ating mode)
Weather-com-
pensated
Weather-compensated: Weather-compensated control based on the heat-
ing curve
Frost protec-
tion temperat-
ure
Off
No frost protection of the HC
0 °C
1 °C
E
E
-15 - 5 °C
If the outside temperature drops below the set value, the system switches
to frost protection operation (the pumps are switched on). The function is
ended if the outside temperature rises above the set value +1 K.
Insulation
Off
Setting the building insulation standard. This influences the averaged out-
side temperature and the automatic adaptations of the heating curve and
the heating times.
-
E
E
low
Normal
Good
very good
Switch temp.
heating circuit
Automatic activation of cooling mode.
Off
1 °C
N
E
Off
Deactivated
10 - 40 °C
If the outside temperature exceeds the set value, the system is switched to
the "Cooling" operating mode. If the outside temperature falls 2 K below the
set value, the system automatically switches back to the previously activ-
ated operating mode
Tab. 7-21
Parameter in menu: "Heating circuit config."
7.6.3
Menu: Heating
[→ Main menu → Configuration → Heating]
Parameters
Setting range
Min / Max
Description
Factory setting Increment Access
BE HF
Heating op-
eration limit
Off
Setting of the automatic summer switch-off of the heating operation. If
the outside temperature measured and averaged by the controller ex-
ceeds the set value by 1 K, the HC is switched off. The heating is re-
leased again if the outside temperature undercuts the set heating limit.
19 °C
1 K
E
E
10 – 40 °C
Heat limit re-
ducing mode
Off
Setting the heating limit for the "switch-off" of the heating circuit during
the setback time (functioning as in [Heating operation limit] parameter).
10 °C
1 K
E
E
10 – 40 °C
Heat-Slope
0.0 - 3.0
Only if [Weather-dependent] parameter = weather-compensated:
Setting of the heating curve. The heating curve reflects the depend-
ence of the target feed temperature of the HC on the outside temperat-
ure (see
).
0.5
0.1
E
E
Feed tem-
perature,
overshoot (*)
0 - 4
This function defines how far the water temperature may exceed the
feed target temperature before the compressor is stopped. The com-
pressor resumes operation when the feed temperature falls below the
target feed temperature. This function ONLY applies to heating mode.
3
1
N
E
Feed tem-
perature
heating
mode
20 – 90 °C
Only if [Weather-dependent] parameter = Weather-compensated:
Setting of the target feed temperature for the heating circuit during the
heating time in operating mode: "Automatic 1", "Automatic 2", "Heat-
ing".
40 °C
1 °C
E
E
Feed tem-
perature re-
ducing mode
10 – 90 °C
Only if [Weather-dependent] parameter = Weather-compensated:
Setting the target feed temperature for the heating circuit during the
setback time for the operating mode: "Automatic 1", "Automatic 2",
"Reducing".
10 °C
1 °C
E
E