4
Function
Operating Instructions
15
Daikin RoCon+ HP
Daikin Controller RoCon+ HP
008.1444299_01 – 09/2018 – EN
Heating circuit auto. 1 and Heating circuit auto. 2
[→ Main menu → Time program → HC auto 1 /HC auto 2]
The time programs for the HC can be parametrised in these menus.
Three switching cycles can be set per day, to which the [Room tem-
perature target 1/2/3] parameters are assigned. Outside the switch-
ing cycles, it is controlled to the [Room temperature reduced] set-
point. The entry can be made separately for each individual weekday
or in week segments.
Hot water auto. 1 and Hot water auto. 2
[→ Main menu → Time program → DHW auto 1 /DHW auto 2]
The time programs for the domestic hot water preparation can be
parametrised in these menus. Three switching cycles can be set per
day, to which the [Hot water temperature, target 1/2/3] parameters
are assigned.
Circulation program
[→ Main menu → Time program → Circulation]
A time program for an optionally connected circulation pump can be
parametrised in this menu. 3 switching cycles per day can be set.
INFORMATION
Use of circulation lines not permitted in France!
Factory settings
The permanent time programs are preset according to
Switching cycle 1
Switching cycle 2
Switching cycle 3
Time period
On
Off
On
Off
On
Off
Room heating
Temperature setting
[Room temperature setpoint 1]:
20 °C
[Room temperature setpoint 2]:
20 °C
[Room temperature setpoint 3]:
20 °C
[Room temperature reduced]: 10 °C
"Heating circuit automatic 1"
Monday - Friday
06:00
22:00
- - : - -
- - : - -
- - : - -
- - : - -
Saturday, Sunday
07:00
23:00
- - : - -
- - : - -
- - : - -
- - : - -
"Heating circuit automatic 2"
Monday - Friday
06:00
08:00
16:00
22:00
- - : - -
- - : - -
Saturday, Sunday
07:00
23:00
- - : - -
- - : - -
- - : - -
- - : - -
Domestic hot water preparation
Temperature setting
[Hot water temp. setpoint 1]: 60 °C
[Hot water temp. setpoint 2]: 60 °C
[Hot water temp. setpoint 3]: 60 °C
"Hot water automatic 1"
Monday - Sunday
05:00
21:00
- - : - -
- - : - -
- - : - -
- - : - -
"Hot water automatic 2"
Monday - Friday
05:00
21:00
- - : - -
- - : - -
- - : - -
- - : - -
Saturday, Sunday
06:00
22:00
- - : - -
- - : - -
- - : - -
- - : - -
"Circulation program"
Monday - Friday
05:00
21:00
- - : - -
- - : - -
- - : - -
- - : - -
Saturday, Sunday
06:00
22:00
- - : - -
- - : - -
- - : - -
- - : - -
Tab. 4-3
Factory setting of the permanent time program
4.3.3
Time program reset
[→ Main menu → Time program → TP reset]
This menu can be used to reset the time programs to factory set-
tings. To do this, select the respective time programs and then con-
firm the selection with the Confirm button on the second menu page.
4.4
Settings
[→ Main menu → Settings]
The basic settings of the controller and the system are made in this
menu. This includes the integration of optional and external compon-
ents. Depending on the access authorisation (user or expert), differ-
ent parameters are available.
4.4.1
Display settings
[→ Main menu → Settings → Display]
This menu can be used to set the following parameters: Language,
date, time, LCD brightness and LCD illumination duration.
Further explanations and possible settings for this menu can be
found in
.
INFORMATION
Increasing the brightness of the LCD display beyond the
factory-set value will reduce the life of the display.