Protection Control
SiUS39-601
52
Function
4.4
Inverter Protection Control
Inverter current protection control and inverter fin temperature control are performed to prevent
tripping due to a malfunction, or transient inverter overcurrent, and fin temperature increase.
[Inverter overcurrent protection control]
[Inverter fin temperature control]
Not limited
Under inverter current
protection control
Inverter current >Ia
Inverter current standby
Inverter
current
> 34A
MgS Reset
OC function
→
MgS off
Inverter current <Ia
INV upper limit frequency = 210 Hz
INV upper limit frequency: 1-step down
from current compressor frequency
INV upper limit frequency: 1-step up from
current compressor frequency
Inverter current >Ia
Inverter current<Ia continues
for 3 min. or more.
Inverter current > Ib continues for 260 sec.
Inverter current > Ic continues for 5 sec.
&
or
Ia
Ib
Ic
25 A
26.1 A
31 A
• When occurring 3 times within 60 min.,
the malfunction code “L8 ” is output.
• When occurring 3 times within 30 min.,
the malfunction code “L9” is output
Not limited
Tfin>183˚F
Fin temp. standby
Tfin<178˚F
INV upper limit frequency = 210 Hz
Under fin temperature
protection control
INV upper limit frequency: 1-step /
1 min down from current compressor
frequency
INV upper limit frequency: 1-step / 1 min
up from current compressor frequency
Interval
Inverter current<178˚F continues
for 3 min. or more.
&
Tfin>183˚F
Tfin>192˚F
• When occurring 3 times within 60 min.,
the malfunction code “L4” is output.
Summary of Contents for BSVQ36MVJU
Page 115: ...Field Setting SiUS39 601 104 Test Operation ...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Page 249: ...Example of Connection SiUS39 601 238 Appendix ...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...