Troubleshooting by Indication on the Remote Controller
SiUS39-601
144
Troubleshooting
2.19
“
E9
”
Outdoor Unit:
Malfunction of Moving Part of Electronic
Expansion Valve (Y1E, Y2E)
Remote
Controller
Display
E9
Applicable
Models
RXYQ72M, 96M
Method of
Malfunction
Detection
Check disconnection of connector
Check continuity of expansion valve coil
Malfunction
Decision
Conditions
Error is generated under no common power supply when the power is on.
Supposed
Causes
Defect of moving part of electronic expansion valve
Defect of outdoor unit PC board (A1P)
Defect of connecting cable
Troubleshooting
(V3067)
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Return to normal?
Turn power supply off, and
turn power supply on again.
Electronic
expansion valve is
connected to X26A or X28A
of outdoor unit
PC board
(A1P).
Normal
when coil
check (
∗
1) of the moving
part of the electronic
expansion valve is
checked.
The connecting
cable is short-circuited or
disconnected.
Replace the connecting cable.
Replace outdoor unit PC board
(A1P).
NO
NO
NO
NO
Replace the moving part of the
electronic expansion valve.
External factor other than
malfunction (for example, noise
etc.).
After connecting, turn the power
off and then back on again.
YES
YES
YES
Summary of Contents for BSVQ36MVJU
Page 115: ...Field Setting SiUS39 601 104 Test Operation ...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Page 249: ...Example of Connection SiUS39 601 238 Appendix ...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Page 269: ...SiUS39 601 iv Index ...