Troubleshooting by Indication on the Remote Controller
SiUS39-601
164
Troubleshooting
Troubleshooting
Output current check
(V2813)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Inverter
output
voltage check
Inverter output voltage
is not balanced.
(Normal if within
±
5V)
Must be measured
when frequency
is stable.
Compressor overload
Inspection of the compressor and
refrigerant system is required.
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
compressor.
NO
Replace the inverter PC board.
YES
NO
Reset and restart.
NO
The secondary
current of the inverter is
higher than 26.1A
for each phase.
Replace the compressor.
NO
YES
Compressor
inspection The
compressor's coil is
disconnected.
YES
YES
Check No.13
Disconnect the the connection
between the compressor and
inverter. Make the power
transistor check mode setting
ON by service mode.
After turning
on again, "L8" blinks
again.
Summary of Contents for BSVQ36MVJU
Page 115: ...Field Setting SiUS39 601 104 Test Operation ...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Page 249: ...Example of Connection SiUS39 601 238 Appendix ...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Page 269: ...SiUS39 601 iv Index ...