SiUS39-601
Specifications
Specifications
13
Slim Ceiling Mounted Duct Type
Notes:
★
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25ft (Horizontal)
★
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
★
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure means
"High static pressure – Standard – Low static pressure".
★
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model
FXDQ07MVJU
FXDQ09MVJU
FXDQ12MVJU
★
1 Cooling Capacity
Btu/h
7,500
9,500
12,000
★
2 Heating Capacity
Btu/h
8,500
10,500
13,500
Casing / Color
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Dimensions: (H×W×D)
in
7-7/8
×
27-9/16
×
24-7/16
7-7/8
×
27-9/16 ×
24-7/16
7-7/8
×
27-9/16 ×
24-7/16
Coil (Cross
Fin Coil)
Rows × Stages × FPI
2
×
12×
17
2
×
12×
17
3
×
12×
17
Face Area
ft²
1.36
1.36
1.36
Fan
Model
—
—
—
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output
HP
0.08
0.08
0.08
Air Flow Rate (H/L)
cfm
280/226 (H/L)
280/226 (H/L)
280/226 (H/L)
External Static Pressure
★
4
Pa
30-10
30-10
30-10
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polyethylene
Foamed Polyethylene
Foamed Polyethylene
Air Filter
Removal, Washable, Mildew Proof
Removal, Washable, Mildew Proof
Removal, Washable, Mildew Proof
Piping
Connections
Liquid Pipes
in
φ
1/4 (Flare Connection)
φ
1/4 (Flare Connection)
φ
1/4 (Flare Connection)
Gas Pipes
in
φ
1/2 (Flare Connection)
φ
1/2 (Flare Connection)
φ
1/2 (Flare Connection)
Drain Pipe
in
VP20
(External Dia. 1-1/32 Internal Dia. 25/32)
VP20
(External Dia. 1-1/32 Internal Dia. 25/32)
VP20
(External Dia. 1-1/32 Internal Dia. 25/32)
Machine Weight (Mass)
Lbs
51
51
51
★
5 Sound Level (H/L)
dBA
33/29
33/29
33/29
Safety Devices
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R-410A Series
R-410A Series
R-410A Series
Standard Accessories
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation for
Fitting, Sealing Pads, Clamps, Screws,
Washers, Conduit Mounting Plate,
Insulation Tube.
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation for
Fitting, Sealing Pads, Clamps, Screws,
Washers, Conduit Mounting Plate,
Insulation Tube.
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation for
Fitting, Sealing Pads, Clamps, Screws,
Washers, Conduit Mounting Plate,
Insulation Tube.
Drawing No.
C:3D051780A
Summary of Contents for BSVQ36MVJU
Page 115: ...Field Setting SiUS39 601 104 Test Operation ...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Page 249: ...Example of Connection SiUS39 601 238 Appendix ...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Page 269: ...SiUS39 601 iv Index ...