Precautions for New Refrigerant (R-410A)
SiUS39-601
252
Precautions for New Refrigerant (R-410A)
2
1/4"
→
5/16" (2min
→
2.5min)
2
No oil is used in pressure test of gauges.
→
For prevention of contamination
2
Temperature scale indicates the relationship between pressure and temperature in gas
saturated state.
Differences
2
Change in pressure
2
Change in service port diameter
7. Charge hose for R-410A
Specifications
2
Working pressure 737 psi (51.8 kg/cm
2
)
2
Rupture pressure 3685 psi (259 kg/cm
2
)
2
Available with and without hand-operate valve that prevents refrigerant from outflow.
Differences
2
Pressure proof hose
2
Change in service port diameter
2
Use of nylon coated material for HFC resistance
8. Weigher for refrigerant charge
Specifications
2
High accuracy
TA101A (for 10-kg cylinder) = ± 2g
TA101B (for 20-kg cylinder) = ± 5g
2
Equipped with pressure-resistant sight glass to check liquid refrigerant charging.
2
A manifold with separate ports for HFCs and previous refrigerants is equipped as standard
accessories.
Differences
2
Measurement is based on weight to prevent change of mixing ratio during charging.
(Hose with ball valve)
Summary of Contents for BSVQ36MVJU
Page 115: ...Field Setting SiUS39 601 104 Test Operation ...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Page 249: ...Example of Connection SiUS39 601 238 Appendix ...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Page 269: ...SiUS39 601 iv Index ...