Special Control
SiUS39-601
40
Function
3.
Special Control
3.1
Startup Control
3.1.1 Startup Control in Cooling Operation
3.1.2 Startup Control in Heating Operation
Actuator
Operation
Remarks
Compressor
Differential pressure control
Compressor operating frequency
increases by 1 step / 20 sec until
Pc - Pe>58 psi
Outdoor unit fan
High pressure control
Initial compressor operating frequency is
set to STEP 1.
1-step increase with Pc>319 psi
1-step decrease with Pc<261 psi
Four way valve
OFF
Main motorized valve (EV1)
0 pls
Subcooling motorized valve (EV2)
0 pls
Hot gas bypass valve (SVP)
ON
Oil equalization valve (SVO)
ON
Receiver gas charging valve (SVL)
OFF
Receiver gas discharging valve (SVG)
OFF
Non-operating unit gas discharging
valve (SVSG)
OFF
Non-operating unit liquid pipe stop valve
(SVSL)
ON
Ending conditions
•
200 sec.
•
Pc - Pe>58 psi
or
Actuator
Operation
Remarks
Compressor
Differential pressure control
Compressor operating frequency
increases by 1 step / 20 sec until
Pc - Pe>58 psi
Outdoor unit fan
STEP9
Four way valve
ON
Main motorized valve (EV1)
200 pls
Subcooling motorized valve (EV2)
0 pls
Hot gas bypass valve (SVP)
ON
Oil equalization valve (SVO)
ON
Receiver gas charging valve (SVL)
OFF
Receiver gas discharging valve (SVG)
OFF
Non-operating unit gas discharging
valve (SVSG)
OFF
Non-operating unit liquid pipe stop valve
(SVSL)
ON
Ending conditions
•
200 sec.
•
Pc - Pe>58 psi
or
Summary of Contents for BSVQ36MVJU
Page 115: ...Field Setting SiUS39 601 104 Test Operation ...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Page 249: ...Example of Connection SiUS39 601 238 Appendix ...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Page 269: ...SiUS39 601 iv Index ...