Troubleshooting by Indication on the Remote Controller
SiUS39-601
168
Troubleshooting
2.38
“
P1
”
Outdoor Unit:
Inverter Over-Ripple Protection
Remote
Controller
Display
P1
Applicable
Models
RXYQ72M, 96M
Method of
Malfunction
Detection
Imbalance in supply voltage is detected in PC board.
Malfunction
Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
Malfunction is not decided while the unit operation is continued.
"P1" will be displayed by pressing the inspection button.
Supposed
Causes
Open phase
Voltage imbalance between phases
Defect of main circuit capacitor
Defect of inverter PC board
Defect of K1M
Improper main circuit wiring