SiUS39-601
Troubleshooting (OP: Schedule Timer)
Troubleshooting
207
4.5
“
MC
”
Address Duplication, Improper Setting
Remote
Controller
Display
MC
Applicable
Models
schedule timer
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Decision
Conditions
When two or more schedule timers are connected.
Supposed
Causes
Address duplication of schedule timer
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2840)
Are two or more
schedule timer
connected?
Reset the power supply for the
schedule timer.
Disconnect all schedule timer
except one and reset the
schedule timer’s power supply.
YES
NO