Troubleshooting by Indication on the Remote Controller
SiUS39-601
126
Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Provide 208~230V power
supply.
YES
NO
Is power supply
208~230V provided?
Replace the limit switch
connecting cable.
Replace indoor unit PC board.
Replace the power supply
connecting cable.
Replace swing motor.
Take the cam mechanism
apart, reassemble and turn on
again.
YES
NO
YES
YES
NO
YES
NO
Connect the connector to X9A
and turn on again.
Replace indoor unit PC board.
NO
NO
YES
NO
YES
NO
YES
YES
NO
Indoor unit
is a model equipped
with a swing flap
function
The swing
motor works when
the power supply is turned
off and then back
on.
When
the air flow
direction flap's cam
mechanism is disconnected
from the swing motor,
operation is normal
when turned
on again.
The connecting cable
has no continuity.
After
turning
the swing-flap
ON and then
stopping with the
remote controller, the
voltage of X6A of the indoor
unit PC board is 208 ~ 230V
when turnedon
again (within 30
seconds of
turning on
again).
The connector
is connected to X9A of
the indoor unit PC
board.
The limit switch
functions normally.
The connecting
cable is short-circuited
or disconnected.
Replace swing motor.
(V2780)
Summary of Contents for BSVQ36MVJU
Page 115: ...Field Setting SiUS39 601 104 Test Operation ...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Page 249: ...Example of Connection SiUS39 601 238 Appendix ...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Page 269: ...SiUS39 601 iv Index ...