SiUS39-601
Troubleshooting by Indication on the Remote Controller
Troubleshooting
145
∗
1 Coil check method for the moving part of the electronic expansion valve
Disconnect the electronic expansion valve from the PC board and check the continuity between the
connector pins.
(Normal)
: Continuity Approx. 300
Ω
{
: Continuity Approx. 150
Ω
× : No continuity
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
1. White
×
Approx.
300
Ω
×
{
Approx.
150
Ω
×
2. Yellow
×
Approx.
300
Ω
×
{
Approx.
150
Ω
3. Orange
×
{
Approx.
150
Ω
×
4. Blue
×
{
Approx.
150
Ω
5. Red
×
6. Brown