SiUS39-601
Troubleshooting by Indication on the Remote Controller
Troubleshooting
151
2.24
“
J2
”
Current Sensor Malfunction
Remote
Controller
Display
J2
Applicable
Models
RXYQ72M, 96M
Method of
Malfunction
Detection
Malfunction is detected according to the current value detected by current sensor.
Malfunction
Decision
Conditions
When the current value detected by current sensor becomes 5A or lower, or 40A or more during
standard compressor operation.
Supposed
Causes
Faulty current sensor
Faulty outdoor unit PC board
Troubleshooting
(V3071)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
current sensor
mounted on the T-phase
wire?
Is the
connector for
current sensor
connected to X30A, X31A
on outdoor unit
PC board
(A1P)?
Replace current sensor and
outdoor unit PC board.
Connect the connector, and
operate unit again.
NO
NO
Mount the current sensor
correctly, and operate unit again.
YES
YES
Summary of Contents for BSVQ36MVJU
Page 115: ...Field Setting SiUS39 601 104 Test Operation ...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Page 249: ...Example of Connection SiUS39 601 238 Appendix ...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Page 269: ...SiUS39 601 iv Index ...