Troubleshooting by Remote Controller
SiUS39-601
116
Troubleshooting
8
: ON
7
: OFF
9
: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Referred
Indoor
Unit
A0
9
9
9
Error of external protection device
120
A1
9
9
9
PC board defect, E
2
PROM defect
121
A3
9
9
9
Malfunction of drain level control system (S1L)
122
A6
9
9
9
Fan motor (M1F) lock, overload
124
A7
8
7
9
Malfunction of swing flap motor (MA)
125
A9
9
9
9
Malfunction of moving part of electronic expansion
valve (20E)
127
AF
8
7
9
Drain level above limit
129
AH
8
7
9
Malfunction of air filter maintenance
—
AJ
9
9
9
Malfunction of capacity setting
130
C4
9
9
9
Malfunction of thermistor (R2T) for heat exchange
(loose connection, disconnection, short circuit,
failure)
131
C5
9
9
9
Malfunction of thermistor (R3T) for gas pipes (loose
connection, disconnection, short circuit, failure)
132
C9
9
9
9
Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
133
CJ
8
8
8
Malfunction of thermostat sensor in remote controller
134
Outdoor
Unit
E1
9
9
9
PC board defect
135
E3
9
9
9
Actuation of high pressure switch
136
E4
9
9
9
Actuation of low pressure sensor
137
E5
9
9
9
Compressor motor lock (INV compressor)
139
E6
9
9
9
Standard compressor lock or over current
141
E7
9
9
9
Malfunction of outdoor unit fan motor
142
E9
9
9
9
Malfunction of moving part of electronic expansion
valve (Y1E~3E)
144
F3
9
9
9
Abnormal discharge pipe temperature
146
F6
9
9
9
Refrigerant overcharged
147
H3
8
7
9
Malfunction of High pressure switch
—
H4
9
9
9
Actuation of Low pressure switch
—
H7
9
9
9
Abnormal outdoor fan motor signal
148
H9
9
9
9
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
150
J2
9
9
9
Current sensor malfunction
151
J3
9
9
9
Malfunction of discharge pipe thermistor (R31~33T)
(loose connection, disconnection, short circuit, failure)
152
J5
9
9
9
Malfunction of thermistor (R2T) for suction pipe (loose
connection, disconnection, short circuit, failure)
153
J6
9
9
9
Malfunction of thermistor (R4T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
154
J7
9
9
9
Malfunction of receiver outlet liquid pipe thermistor (R6T)
155
J8
9
9
9
Malfunction of thermistor (R7T) for oil equalizing pipe.
(loose connection, disconnection, short circuit,
failure)
156
J9
9
9
9
Malfunction of sub-cooling heat exchanger gas pipe
thermistor (R5T)
157
JA
9
9
9
Malfunction of discharge pipe pressure sensor
158
JC
9
9
9
Malfunction of suction pipe pressure sensor
160
L0
9
9
9
Inverter system error
—
L4
9
9
9
Malfunction of inverter radiating fin temperature rise
161
L5
9
9
9
Inverter compressor motor grounding, short circuit
162
L6
9
9
9
Compressor motor coil grounding on short circuit
—
L8
9
9
9
Inverter current abnormal
163
L9
9
9
9
Inverter start up error
165
Summary of Contents for BSVQ36MVJU
Page 115: ...Field Setting SiUS39 601 104 Test Operation ...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Page 249: ...Example of Connection SiUS39 601 238 Appendix ...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Page 269: ...SiUS39 601 iv Index ...