Troubleshooting by Indication on the Remote Controller
SiUS39-601
192
Troubleshooting
2.54
“
UH
”
Malfunction of System, Refrigerant System Address
Undefined
Remote
Controller
Display
UH
Applicable
Models
All models of indoor units
RXYQ72M, 96M
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Improper connection of transmission wiring between indoor - outdoor unit and outdoor - outdoor
unit.
Defect of indoor unit PC board
Defect of outdoor unit PC board (A1P)