SiUS39-601
Troubleshooting (OP: Schedule Timer)
Troubleshooting
201
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2836)
Is
the power supply
turned on for indoor
units displaying
malfunction?
Is
transmission wiring
disconnected or wired
incorrectly?
Is
the transmission
wiring with the master
controller disconnected or
wired incorrectly?
Is
the master controller's
connector for setting
master controller
disconnected?
Set the group No. correctly.
Replace indoor unit PC board.
Fix the wiring correctly.
Fix the wiring correctly.
Connect the connector
correctly.
Replace the schedule timer.
Reset power supply
simultaneously for all optional
controllers for centralized
control.
NO
YES
NO
YES
YES
NO
NO
Turn indoor unit's power
supply.
YES
NO
NO
YES
YES
YES
NO
Has
an indoor unit
once connected been
removed or its address
changed?
Is the group
No. of malfunctioning
indoor units set?
Is
transmission with all
indoor units
malfunctioning?
Summary of Contents for BSVQ36MVJU
Page 115: ...Field Setting SiUS39 601 104 Test Operation ...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Page 249: ...Example of Connection SiUS39 601 238 Appendix ...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Page 269: ...SiUS39 601 iv Index ...