SiUS39-601
Field Setting
Test Operation
81
3.2
Field Setting from Outdoor Unit
3.2.1
Field Setting from Outdoor Unit
Setting by dip switches
The following field settings are made by dip switches on PC board.
Dipswitch
Setting item
Description
No.
Setting
DS1-1
ON
Cool / Heat select
Used to set cool / heat select by remote controller
equipped with outdoor unit.
OFF (Factory set)
DS1-2
~DS1-4
ON
Not used
Do not change the factory settings.
OFF (Factory set)
DS2-1
~4
ON
Not used
Do not change the factory settings.
OFF (Factory set)
DS3-1, 2
ON
Not used
Do not change the factory settings.
OFF (Factory set)
Caution
DIP switch Setting after changing the main P.C.Board(A1P) to spare parts P.C.B.
When you change the main P.C.Board(A1P) to spare parts P.C.B., please carry out the following
setting.
DIP Switch Detail
∗
If the DS1-4,DS2-1 setting(refrigerant classification) has not been carried out, error code
“UA” is displayed and unit can not be operated.
DS No.
Item
Contents
DS1-1
Cool/Heat change
over setting
ON
The Cool/Heat change over setting is carried out by COOL/
HEAT changeover remote controller fitted to outdoor unit.
OFF
The Cool/Heat change over setting is not carried out by COOL/
HEAT changeover remote controller fitted to outdoor unit.
DS1-2
Power supply
setting
ON
3 phase 200 Volt area
OFF
3 phase 400 Volt area
DS1-3
Cooling only/Heat-
pump setting
ON
Cooling only
OFF
Heat-pump
DS1-4
Refrigerant
classification
DS2-1
DS2-2
Capacity setting
DS2-3
DS2-4
1 2 3 4
1 2 3 4
DS1
DS2
ON
OFF
ON
OFF
R-22
Not used
R-410A
DS1-4
OFF
ON
OFF
DS2-1
OFF
OFF
ON
72, 96
DS2-2
OFF
DS2-3
OFF
DS2-4
ON
Summary of Contents for BSVQ36MVJU
Page 115: ...Field Setting SiUS39 601 104 Test Operation ...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Page 249: ...Example of Connection SiUS39 601 238 Appendix ...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Page 269: ...SiUS39 601 iv Index ...