Troubleshooting - Outdoor Unit Related
Si18-201
268
Service Diagnosis
3.3.6
Operation Halt Due to Discharge Pipe Temperature Control
Outdoor Unit
Indication
F3
Method of
Malfunction
Detection
Discharge pipe temperature control (halt, frequency deviation, etc.) is carried out using
temperature detected by the discharge pipe thermistor.
Malfunction
Decision
Conditions
"
Case where the compressor halts operation when the temperature detected by the
discharge pipe thermistor rose to 115°C or higher. (reset when the temperature falls to 85°C
or lower.)
"
When this is generated 4 times, the system shuts down.
"
The error counter resets itself when no compressor abnormality occurs within 60-minute
cumulative time after the error generation.
(including operation halt due to other errors)
Supposed
Causes
"
Insufficient refrigerant
"
Malfunction of 4-way valve
"
Faulty discharge pipe thermistor
"
Faulty outdoor unit PC board
"
Water mixed in the piping at site
"
Faulty motorized valve
"
Faulty stop valve
"
Faulty indoor unit solenoid valve
Troubleshooting
Check No.8
Refer to P.305
Check No.3
Refer to P.301
Check No.9
Refer to P.306
Correctly place the
thermistor in the discharge
pipe.
Replace thermistor.
Replace the main unit, coil
of motor operated valve.
Refer to REMEDY for
Refrigerant system check.
Replace PC board.
Is discharge pipe
thermistor disconnected?
(MF025)
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check No. 8
Thermistor check
Faulty
NO
Check No. 3
Motorized valve check
Faulty
Check No. 9
Refrigerant system check
Faulty
OK
OK
OK
· Insufficient refrigerant
· Malfunction of 4-way valve
· Water content mixed
· Faulty stop valve
Summary of Contents for BPMK928B42
Page 9: ...Si18 201 viii Table of Contents ...
Page 71: ...Specifications Si18 201 58 Specifications ...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Page 214: ...Si18 201 Remote Controller Operations 201 ...
Page 216: ...Si18 201 Remote Controller Operations 203 ...
Page 217: ...Remote Controller Si18 201 204 Operations ...
Page 237: ...Method of Field Set Si18 201 224 Operating Test ...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...