Method of Field Set
Si18-201
214
Operating Test
2.1.2 Local Setting Mode No.
Example
To set the filter sign time to “filter contamination - heavy” for all units in a group:
Set mode No. to “10,” setting switch No. to “0,” and setting position No. to “02.”
Table
Notes:
1. Setting is made in all units in a group. To set for individual indoor units or to check the
setting, use the mode Nos. (with “2” in upper digit) in parentheses ( ).
2. The setting position No. is set to “01” at the factory, except for the following cases in which
“02” is set.
"
Setting of air flow direction adjustment range
"
Automatic restart after power outage.
"
Remote control thermostat
"
Filter sign indication (only for ceiling-mounted duct type)
Mode
No.
Note 1
Setting
Switch
No.
Setting Description
Setting Position No. *Note 2
01
02
03
10(20)
0
Filter contamination - heavy /
light (Setting of operating hours
for filter sign indication)
(Change setting when reducing
filter sign indication time to half
due to quick soiling of filter)
Ultra-Long-
Life Type
Light
Approx.
10,000
hours
Heavy
Approx.
5,000
hours
—
Long-Life
Type
Approx.
2,500
hours
Approx.
1,250
hours
Standard
Type
Approx.
200
hours
Approx.
100
hours
1
Long-life filter type (Setting of filter sign
indication time)
(Change setting when Ultra-long-life filter is
installed)
Long-Life Filter
Ultra-Long-Life
Filter (1)
Setting Description
Ultra-Long-Life
Filter (2)
3
Estimation of filter operating hour
(Change setting when filter sign indication is
not used)
ON
OFF
—
11(21)
0
No. of Sky Air indoor units connected for
simultaneous ON-OFF multi system
(Change setting when simultaneous
operation multi system is used) *Note 3
Pair
Twin
Triple
1
Simultaneous operation multi-unit individual
setting
Unified
Individual
—
2
Indoor unit fan OFF when cooling/heating is
OFF
—
Fan OFF
—
12(22)
3
Change to set fan speed when heater
thermostat is OFF *Note 5
Fan Speed LL
Set Fan Speed
—
5
Automatic restart after power outage reset
*Note 6
OFF
ON
—
13(23)
0
High
Ceiling
Ceiling-mounted built-in multi-flow
cassette type, Ceiling suspended
cassette type
N
H
S
Ceiling-suspended type, wall-
mounted type
2.7 m or Lower
2.7~3.5 m
—
Fan speed increase (wall-mounted type)
Standard
Slight Increase
Normal Increase
1
Air flow direction selection (Change setting
when blocking kit is installed) *Note 4
F
T
W
3
Air flow direction adjustment (Change setting
when decorative air outlet panel is installed)
Installed
Not Installed
—
4
Setting of air flow direction adjustment range
Upward
Standard
Downward
5
On-site fan speed change by air outlet
(When using phase control)
Standard
Option 1
Option 2
6
External static pressure setting (To be set
according to connected duct resistance)
(High ceiling setting in the case of FHYK)
Standard
(Standard)
High Static
Pressure (High
Ceiling Setting)
Low Static Pressure
Summary of Contents for BPMK928B42
Page 9: ...Si18 201 viii Table of Contents ...
Page 71: ...Specifications Si18 201 58 Specifications ...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Page 214: ...Si18 201 Remote Controller Operations 201 ...
Page 216: ...Si18 201 Remote Controller Operations 203 ...
Page 217: ...Remote Controller Si18 201 204 Operations ...
Page 237: ...Method of Field Set Si18 201 224 Operating Test ...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...