System control
Main Functions
131
3.15
Discharge Pipe Control
Outline
With the internal compressor temperature used as a substitute of the discharge pipe
temperature, when the
discharge pipe temperature exceeds the specified level, the discharge pipe control regulates
the upper limit of the output frequency to prevent the internal pressure from rising.
(This function serves the same purpose as the discharge pipe high temperature control that
regulates the motorized valve.)
Details
With each operation of the discharge pipe temperature malfunction operation counter, the
above zone judgment temperature is decreased by 2.5°C.
Drooping speed : 4Hz/60sec
Reset zone
Abnormal reset
temperature
No-change zone
Drooping zone
: 100˚C
: 105˚C
(105)
: 115˚C
Discharge pipe temp.
: 100˚C
: 103˚C
(M1020)
Stop zone
Summary of Contents for BPMK928B42
Page 9: ...Si18 201 viii Table of Contents ...
Page 71: ...Specifications Si18 201 58 Specifications ...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Page 214: ...Si18 201 Remote Controller Operations 201 ...
Page 216: ...Si18 201 Remote Controller Operations 203 ...
Page 217: ...Remote Controller Si18 201 204 Operations ...
Page 237: ...Method of Field Set Si18 201 224 Operating Test ...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...