Method of Field Set
Si18-201
220
Operating Test
2.2
Group Number Setting for Central Remote Control
"
When controlled by a central remote controller and an unified ON/OFF controller, the group
number setting in each group is required.
"
Carry out the setting after the central remote controller, the unified ON/OFF controller, and
the indoor units are powered on.
Group number setting for central remote control by a remote controller
<In case of Room Airconditioner>
The number is set by the dip switch on the PC board of interface adaptor for Room
Airconditioners.
<In case of SkyAir>
1. Power onto the indoor units and the unified ON/OFF controller. Make sure if there are any
trouble about the installation and the electric wiring or not before the power-on. (when the
power is ON, there will sometimes happen the case that it will become the state which once
all lumps will turn on before the central control lump will turn on in approx. one minute,
rejecting the handling for the control(blinking as repeating two times ON and one time OFF).
2. Hold down “
” button for a minimum of 4 seconds, and then the remote controller will
enter the FIELD SET MODE.
3. Select the MODE No. “
00
” with “
” button.
4. Use “
” button to select the group No. for each group.
(Group numbers advance in the order of 1-00, 1-01, ... 1-15, 2-00, ... 8-15.)
5. Press “
” to set the selected group No.
6. Press “
” to return to NORMAL MODE.
"
Group number setting example
Note:
1. F1, F2 mark : Interface adaptor for Room Airconditioners or SkyAir.
2. In case of SkyAir without a remote controller, once connect a remote controller with SkyAir to
set the group No. for the central remote control and then remove the remote controller.
Summary of Contents for BPMK928B42
Page 9: ...Si18 201 viii Table of Contents ...
Page 71: ...Specifications Si18 201 58 Specifications ...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Page 214: ...Si18 201 Remote Controller Operations 201 ...
Page 216: ...Si18 201 Remote Controller Operations 203 ...
Page 217: ...Remote Controller Si18 201 204 Operations ...
Page 237: ...Method of Field Set Si18 201 224 Operating Test ...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...