Si18-201
Operating Test
Operating Test
209
1.2
Test Operation Switch
TEST OPERATION SWITCH [SW7]
Press the FORCED OPERATION SWITCH [SW7]
Aftrer sellecting the COOL/HEAT SWITCH [SW3]
<CAUTIONS>
1) Test operation stops automatically in about
60 minutes
.
2) Cooling test operation cannot be performed if the outside air temperature is
–5˚C or lower
.
3) Operate SkyAir indoor unit in the same mode.
[TO CONTINUE TEST OPERATION]
Press the TEST SW [SW7] again.
[TO RESET TEST OPERATION]
Press the TEST SW [SW7], wait at least 3 seconds and press the TEST SW again.
Digital display:
"
"
Blinking
(Q0001)
Summary of Contents for BPMK928B42
Page 9: ...Si18 201 viii Table of Contents ...
Page 71: ...Specifications Si18 201 58 Specifications ...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Page 214: ...Si18 201 Remote Controller Operations 201 ...
Page 216: ...Si18 201 Remote Controller Operations 203 ...
Page 217: ...Remote Controller Si18 201 204 Operations ...
Page 237: ...Method of Field Set Si18 201 224 Operating Test ...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...