Si18-201
System control
Main Functions
111
3.3
Standby Control at Power ON
Purpose of the
Function
To initialize the motorized valve at power ON, to determine the valve opening degree and
promote pressure equalization, and to conduct a standby operation.
The reason for promoting pressure equalization at power ON is to prevent the compressor from
locking due to insufficient pressure equalization that could result if units are restarted
immediately after reset during operation (due to momentary power outage and others). The
standby operation collects refrigerant in the receiver to ensure sufficient oil level and dilution in
the compressor immediately after startup.
∗
The standby operation and pressure equalization are described in the next section.
Explanation of
The Function
[Detail]
1. Compressor ON prohibit timer (60 seconds) starts when power is turned on.
P1 pulses is closed, and the current opening degree is set to 0 pulse (full closing process)
2. Compressor ON prohibit timer reaches the set time, a standby operation is activated.
Note
When the compressor ON prohibit timer is in counting operation, operation of the compressor is
prohibited.
During standby operation, operation command from BP units are ignored.
Note
Regarding initialization of BP motorized valves at power ON, refer to the section on BP
motorized valve full closing on page 153.
EVP
Power ON
P1
P2
Fully closed
Fully closed
Fully closed
EVL
P1
EVG
P1
Full closing
process
60 sec
Shifts to standby operation
or to stop status.
(M1004)
Compressor ON
prohibit timer
Summary of Contents for BPMK928B42
Page 9: ...Si18 201 viii Table of Contents ...
Page 71: ...Specifications Si18 201 58 Specifications ...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Page 214: ...Si18 201 Remote Controller Operations 201 ...
Page 216: ...Si18 201 Remote Controller Operations 203 ...
Page 217: ...Remote Controller Si18 201 204 Operations ...
Page 237: ...Method of Field Set Si18 201 224 Operating Test ...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...