Troubleshooting - Outdoor Unit Related
Si18-201
262
Service Diagnosis
3.2
7 Seg. Display on the Outdoor P. C. Board
TROUBLE DAIGNOSIS
<
LED ON OUTDOOR UNIT PCB
>
<
DIGITAL DISPLAY
>
R o t a r y S W p o s i t i o n : S e t S W 1 t o 0 , S e t S W 2 t o 0 .
L E D D I S P L A Y
[ GREEN ]
DIGITAL
DISPLAY
DIAGNOSIS
[ ON ] OR [ OFF ] OR
[ B l i n k i n g q u i c k l y ]
[ Blinking
slowly ]
NORMAL
ABNORMAL
(Malfunction of control unit)
PCB4
A 5
INDOOR UNNIT : High pressure protector
worked, or freeze-up in operating unit
(Stop due to peak cut, freeze)
BP UNIT : Malfunction of moving part of
electoric expansion valve (Y1E ~ Y4E)
OUTDOOR UNIT : Actuation of high
pressure switch
OUTDOOR UNIT : Fan motor lock or OCP
(Output Over current Protect)
OUTDOOR UNIT : Inverter input over
current protect
OUTDOOR UNIT : Abnormal discharge pipe
temperature
OUTDOOR UNIT : High pressure switch
failure
OUTDOOR UNIT : Compressor motor
position detection sensor error
OUTDOOR UNIT : Fan motor position
detection sensor error
OUTDOOR UNIT : Malfunction of
thermistor for outdoor air
OUTDOOR UNIT : Discharge pipe thermistor
or related abnormaly
OUTDOOR UNIT : Malfunction of suction
pipe thermistor
OUTDOOR UNIT : Malfunction of heat
exchanger thermistor
OUTDOOR UNIT : Malfunction of heat
exchanger liquid thermistor
BP UNIT : Malfunction of liquid
pipe thermistor
BP UNIT : Malfunction of gas pipe
thermistor
OUTDOOR UNIT : Malfunction of suction
pipe pressure sensor
OUTDOOR UNIT : Electoric component box
over temperature
OUTDOOR UNIT : Radiation fin over
temperature
OUTDOOR UNIT : Compressor overload,
compressor motor wire cut
OUTDOOR UNIT : Malfunction of
electoric component box sensor
OUTDOOR UNIT : Malfunction of power
unit temperature sensor
OUTDOOR UNIT : Power supply
insurfficient or instantaneous failure
<
CAUTION
>
It is possible to check if the outdoor unit, or a
BP unit, is malfunctioning.
Rotary SW position : Set SW1 to 0, Set SW2 to 1.
(Digital display is as follows.)
Malfunction of transmission between
BP unit and outdoor unit
Malfunction of transmission between
indoor unit and BP unit
OUTDOOR UNIT : Refrigerant shortage
OUTDOOR UNIT : Compressor start up error
OUTDOOR UNIT : Total input over current
OUTDOOR UNIT : Compressor motor
insulation defect, short circuit,
power unit short circuit
OUTDOOR UNIT : Malfunction of
transmission between inverter and
outdoor control unit
OUTDOOR UNIT : AC current sensor error
OUTDOOR UNIT : Low pressure drop error
OUTDOOR UNIT : Malfunction of moving
part of electoric expansion valve
(Y1E ~ Y3E)
OUTDOOR UNIT : Compressor lock
A 9
E 3
E 6
E 7
E 8
E 9
F 3
F C
H 3
H 6
H 7
H 8
H 9
J 3
J 5
J 6
J 7
J 8
J 9
J C
L 3
L 4
L 5
L 7
L 8
L 9
L C
P 3
P 4
U 0
U 2
U 4
U 6
LED (A)H1P
LED H2P
LED H3P
LED H4P
PCB1
PCB3
Outdoor unit malfunction :
BP unit malfunction
:
,
,
DC fan malfunction
:
Return SW to original position. : "SW1 to 0, SW2 to 0"
(UPPER)
(LOWER)
BP UNIT : Failure of field setting
OUTDOOR UNIT : Malfunction of outdoor
control unit
Malfunction of transmission between
fan control unit and outdoor control
unit
U 7
U A
U H
2P060527
Switch Box
Service Monitor
7 seg. display
Summary of Contents for BPMK928B42
Page 9: ...Si18 201 viii Table of Contents ...
Page 71: ...Specifications Si18 201 58 Specifications ...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Page 214: ...Si18 201 Remote Controller Operations 201 ...
Page 216: ...Si18 201 Remote Controller Operations 203 ...
Page 217: ...Remote Controller Si18 201 204 Operations ...
Page 237: ...Method of Field Set Si18 201 224 Operating Test ...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...