281
3.3.19
Abnormal LP Error
Outdoor Unit
Indication
JC
Method of
Malfunction
Detection
1. Error is determined by the LP sensor value when the compressor is off.
2. Error is determined by the LP sensor value in normal operation when the compressor is on.
3. Error is determined by the LP sensor value when a certain time range passed after standby
operation at time of starting.
Malfunction
Decision
Conditions
When either of 1-3 conditions mentioned above was satisfied.
Supposed
Causes
"
Defective LP sensor
"
Faulty connectors connection of LP sensor
"
Possibility of gas shortage
"
When cooling: Refrigerant amount 0-20%
"
When heating: Refrigerant amount 0-5%
Troubleshooting
Start
Check LP sensor
connectors.
Check stop valve.
Charge with the proper
amount of refrigerant.
Could be outside causes
other than defect.
Probe where the noise
comes from and take
remedy.
Replace LP sensor after
collecting refrigerant and
charge with refrigerant.
(MF038)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check LP sensor connectors.
Is it normal?
NO
Is the stop valve open?
YES
YES
NO
Is gas lacking?
YES
Does
the LP sensor value
vary in any operative
status?
NO
NO
YES
Faulty LP sensor
Summary of Contents for BPMK928B42
Page 9: ...Si18 201 viii Table of Contents ...
Page 71: ...Specifications Si18 201 58 Specifications ...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Page 214: ...Si18 201 Remote Controller Operations 201 ...
Page 216: ...Si18 201 Remote Controller Operations 203 ...
Page 217: ...Remote Controller Si18 201 204 Operations ...
Page 237: ...Method of Field Set Si18 201 224 Operating Test ...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...