Si18-201
Troubleshooting - Outdoor Unit Related
Service Diagnosis
273
3.3.11
Operation Halt Due to Detection of CT Error
Outdoor Unit
Indication
H8
Method of
Malfunction
Detection
CT errors are detected using the compressor’s operating frequency and the input current
detected by the CT.
Malfunction
Decision
Conditions
When the compressor’s rotating speed is 64rps or more and the CT input is 2 A or less.
"
When a CT error is generated 4 times, the system shuts down.
(The 4-time counter resets itself when no outdoor unit abnormality occurs within 60 minutes
(cumulative time) after the error generation.)
Supposed
Causes
"
Incorrect connectors connection
"
Faulty thermistor
"
Faulty power transistor
"
Breaking of wire or faulty connection of internal wiring
"
Faulty reactor
"
Faulty PCB
Troubleshooting
Check No.11
Refer to P.307
Check No.5
Refer to P.302
Turn the power on again to
re-start the equipment.
YES
Replace the outdoor unit
PCB.
(Control PCB, Filter PCB)
Correct the internal wiring.
Replace the compressor.
Replace the outdoor unit
PCB.
(Control PCB, Filter PCB)
Is the current
less than 2.00A?
Is it normal?
(MF030)
NO
YES
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check No. 11
Input current measurement
Check No. 5
Internal wiring check (1)
Is it normal?
NO
Check the conductivity of the
compressor coil.
YES
Summary of Contents for BPMK928B42
Page 9: ...Si18 201 viii Table of Contents ...
Page 71: ...Specifications Si18 201 58 Specifications ...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Page 214: ...Si18 201 Remote Controller Operations 201 ...
Page 216: ...Si18 201 Remote Controller Operations 203 ...
Page 217: ...Remote Controller Si18 201 204 Operations ...
Page 237: ...Method of Field Set Si18 201 224 Operating Test ...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...