System control
Si18-201
148
Main Functions
3.26.3 Outdoor Unit Motorized Valve Control in Startup and During the
Number of Operating Room Units Change
Outline
This function improves the convergibility of refrigerating cycle during startup (operation
startup, when the number of operating room unit changes, in thermostat reset).
It also ensures sufficient oil level for compressor startup (low-temperature heating operation
start).
The adverse effects caused by the motorized valve opening to the operation control in startup
are as follows.
When the motorized valve opening is more than the appropriate degree;
Poor control of refrigerant flowing noise (due to lack of subcooling, the convergibility is
insufficient)
(HP does not increase, LP does not decrease
→
no warm/cool air).
Prolonged wet operation (presently no standard set for wet operation).
When the motorized valve opening is less than the appropriate degree;
Prolonged pull-down (increase of compressor internal temperature).
Reduced oil return (low oil level).
Rotor due condensation during cooling.
Details
Initial opening of outdoor unit motorized valve.
Initial opening of outdoor unit motorized valve during cooling operation is according to the
followings:
KBP = FPIMN / initial frequency
"
In case of FPIMN / initial frequency < 1.2
When initial frequency is larger than FPIMN/1.2 = 0.83
EVL = 0
EVG = 50
EVP = 0
"
In case of 1.2
≤
FPIMN / initial frequency
When initial frequency is equal or smaller than FPIMN/1.2 = 0.83
EVL = 52
EVG = 90
EVP = 330 × KBP - 346
Initial opening of outdoor unit motorized valve during heating operation is according to the
followings:
KBP = FPIMN/initial frequency
"
In case of FPIMN / initial frequency < 1
When initial frequency is larger than FPIMN,
EVL = 52
EVG = 60
EVP = 0
"
In case of 1
≤
FPIMN / initial frequency < 1.5
When initial frequency is between 0.67 (= FPIMN/1.5) and 1,
EVL = 52
EVG = 260 × KBP + 60
EVP = 0
Summary of Contents for BPMK928B42
Page 9: ...Si18 201 viii Table of Contents ...
Page 71: ...Specifications Si18 201 58 Specifications ...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Page 214: ...Si18 201 Remote Controller Operations 201 ...
Page 216: ...Si18 201 Remote Controller Operations 203 ...
Page 217: ...Remote Controller Si18 201 204 Operations ...
Page 237: ...Method of Field Set Si18 201 224 Operating Test ...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...