OPERATOR
INTERFACE
SCREENS:
CONFIG
SCREEN
Time SP
– The desired hold time the wash conditions need to be met
before the system can move on to the next wash phase .
Temp SP
–The Caustic and Acid wash phases require a temperature
setpoint be reached before the timer can count down .
Cond SP
– The desired SP of the chemical conductivity level for the
desired concentration . Caustic and Acid Phases must be over their configured
setpoints; Pre-Rinse, Rinse, Final-Rinse and Sanitizer phases must be below their
configured setpoints .
Flow SP
– The desired flow rate of the CIP system for all wash phases .
Chem SP
– If the system is configured for automated chemical dosing,
the following settings appear . (Note: This system is designed to pulse in
small amounts of chemicals at a time and bring the whole CIP loop up to
concentration rather than initially dosing a large amount of chemicals and
potentially overshooting concentration targets .)
Cycle Time
– How often the chemical pump doses chemical during a
Caustic or Acid wash phase . (Default is 10 seconds .)
Pulse Caustic
– How long the chemical pump stays on when it doses
chemicals during a Caustic wash phase . (Default is 2 seconds .)
Pulse Acid
– How long the chemical pump stays on when it doses
chemicals during a Acid wash phase . (Default is 2 seconds .)
Caustic Pump Runtime
– A time setting that will allow the caustic pump to
run for a set amount of time and shut off, rather than looking to achieve a set
conductivity level .
Acid Pump Runtime
– A time setting that will allow the acid pump to
run for a set amount of time and shut off, rather than looking to achieve a set
conductivity level .