E-STOP
INTERLOCK – CHEMICAL PUMPS (IF EQUIPPED)
The chemical pumps have the following interlock criteria that need to be met
prior to them being allowed to operate .
1 . The system is not in an E-Stop condition .
2 . The heater is not in Alarm .
3 . The CIP system is in a Running State status .
4 . The CIP supply flow is greater than 10gpm .
5 . The CIP Return chemical conductivity is less than 100mS/cm .
E-STOP ACTIVE
The system is powered on and the E-Stop button has been activated . The sys-
tem shuts down and inhibits all devices from operating until the E-Stop button is
released by the operator turning the button clockwise . An E-Stop active status
appears on the screen .
ALARM STATUS:
INTERLOCKS