CEAG Notlichtsysteme GmbH
36
Installation
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
6.3 Installation
Isolate all connecting cables and lock them out (e. g. by removing all fuses and proper securing of the mains
supply distribution board using warning signage and/or locks).
Run the connecting cables to the control cabinet position with an adequate length allowance (e. g. for installation
in the cable trunking inside the cabinet). This work must be carried out properly according to the relevant stan-
dards and codes of practice.
Secure all cable entries with the M-type glands provided.
NOTES!
This figure shows the outgoing cables for the mains
supply of slave stations mounted on C-section rails
on the cabinet wall (part no. 400 71 347 126) using
appropriate cleats. Leave no connecting cables
temporarily
loose
and
unsecured!
Subsequent additions or modifications to the component layout are possible; such work on the internal layout of
the cabinet is not described in this manual however as is must be carried out by specially trained CEAG engineers!
The installation and connection of the general lighting system is not described in this manual. Lighting equipment
must be assembled, run and connected according to the relevant electrical engineering standards and codes of
practice. You must also comply with all standards and directives of the country in which the system is installed
and operated.
6.4 Connection to mains
6.4.1 Connection to mains supply of a AT-S
+
station
Power supply of a AT S
+
system is via the supply grid of the power source for safety services.
Load disconnector (1) (terminal box and fuse
box for the mains supply)
Outgoing distributor (2)
Cabinet distributor (3)
N-terminal block (4)
PE-terminal block (5)
Connections shown with load disconnector cover removed
Connection cables for the busbar (mains) at the back (6),
mains supply feeders for the AT-S
+
C station (7),
outgoing feeders for the mains supply of AT-S
+
S (8)
1
4
2
3
5
6
7
8
NOTE:
Do not close the
cabinet door if
the load break
switch is open, as
the door may hit
against it.