CEAG Notlichtsysteme GmbH
18
Construction and Function
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
t > 100ms
t > 1s
Control inputs
The 24V analog inputs Z1 ... Z4 are to control the external control panels, a programmable trip of operational
functions (e. g. bloc / release system, manual reset, etc.) is given.
Optional inputs Z1 - Z4
Z1
Z2
Z3
Z4
Comments:
No function
-
factory setting
Switch
Level triggered (by use of a switch)
24VDC = ON, 0V = OFF
Used as a switch and switches the
circuit or the luminaires with “S”
function.
Switch inverted
Level triggered (by use of a switch)
24VDC = OFF, 0V = ON
Manual reset
Edge triggered (by use of a push switch)
LOW
HIGH
To reset the circuit arrangement
”manual reset“.
Start functiontest
Start a function test.
All luminaires on
Level triggered (by use of a switch)
24VDC = ON, 0V = OFF
For switching on all luminaires
F-Test cancellation
Edge triggered (by use of a push switch)
LOW
HIGH
Cancel function test
Block device
Block / Release function of mains/
emergency lighting during shut
downs.
Maintained off
Switch off all luminaires /circuits,
which are programmed as maintai-
ned light.
Non-maintained on
Switch on all luminaires /circuits,
which are programmed as non-
maintained light.
Ventilator monitor
Level triggered (by use of a switch)
24VDC = OK, 0V = Failure
Set charging failure at the potential-
free relay contacts of the control
module to the CG IV relay module
and the CGVision, as long as 0 V is
present.
Ext. ISO monitor
Ext. Battery monitor
Ext. Monitor
Ext. Source ready
Level triggered (by use of a switch)
24VDC = normal operation, 0V = not ready
Sets „Ready“ at the potential-free
relay contacts of the control module
and the CGVision, as long as 24 V
DC is present.
Ext. Source active
Level triggered (by use of a switch)
24VDC = ext. Source active
0V = normal operation
Sets „Ext. Source active“ at the
potential-free relay contacts of the
control module and the CGVision, as
long as 24 V DC is present.
Ext. Source failure
Level triggered (by use of a switch)
24VDC = normal operation
0V = failure
Sets „Ext. Source failue“ at the
potential-free relay contacts of the
control module and the CGVision, as
long as 0 V is present.
Level trigger:
Edge trigger:
Z1 to Z4, connection for analogue inputs:
4 freely assignable 24 V analogue inputs, can
be programmed either inverted or non-inverted