CEAG Notlichtsysteme GmbH
24
Construction and Function
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
4.4.5 External TLS-bus-module
This module monitors the switching status of buttons for up to two separate stairwell illuminations and transmitts
the particular switching status via a RS-485-busline to the controller of the system AT-S
+
.
In mains and emergency operation the circuits of stairlight and emergency light will be operated according to the
settings for the controller CU-S
+
! In addition to this, a supply of the switcher glow lamps of the connected buttons
in mains and emergency operations occurs.
Technical Data
Mains supply for the modules
– Device: 24 V DC (19 ... max. 30 V)
– Cable type: 4 x 2 x 0,8 mm IY(ST)Y, Twistet Pair screended (minimum standard).
– Current consumption: max 50 mA, depending on the number of the connected glow lamps for stairwell-light
switcher
Bus connection
– RS 485
– Rated current: U
n
= 24 V DC
– Cable type: 4 x 2 x 0,8 mm IY(ST)Y, Twistet Pair screened (minimum standard).
– Connecting terminals A, B, SE
2 switching outputs
– Rated current U
n
= 230 V
– Switched current: max. 10 A (120 A/ms)
Application
Assembly in the subdistribution board of the monitored
circuits due to the low laying effort for the illumination
circuits (compare «Mounting and Connection of
external bus modules»).
Assembly in the control cabinet AT S
+
C (AT S
+
S) due
to reasons for simplification of the maintenance
(compare «Mounting and Connection of external bus
modules»).
Application-environment
Protection class / -category: IP20 / I
Ambient temp.: -10 ... +40°C
1
2
3
4
5
Pos. 1:top connection terminal
Pos. 2: lower connection terminal
Pos. 3: Display-LEDs
LED K1 resp. K2 lights up when the circuit is connected.
LED T1 and T2 light up as long as the corresponding button-
input is switched.
LED
E
in
/O
n
lights up when 24 V DCsupply voltage is present
and the device is activated over the controller.
LED
S
törung
/F
ailurE
lights up when a fault function was regi-
strated by the module
Pos. 4: Locking device button for a module attached to a 35
mm-DIN mountingrail
Pos. 5: Bus address
Summary of Contents for Ceag AT-S+ C0