CEAG Notlichtsysteme GmbH
60
Operating
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
8.4.5 Menu 5: “Circuit setup”
Overview:
Main menu
Test & status menu
Block,reset
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Memory card
Menu 5
Deactivate module
Search ext. modules
Text assignment
DLS/TLS-Assignment
Selection of
menu options
with the keys
<ok>:
confirm selec-
tion
<Menu>: can-
cel and return
to the
previous
menu (any
changes
entered are
saved)
<ESC>: cancel
and return to
the
previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
Menu 5.1:
<ok>
Successive selection of the installed
modules with
Numbering is consecutive.
<ok>: The displayed module is deac-
tivated.
Finish and return to Menu 5 with
<Menu>
Notes:
This menu function must be run when
removing modules.
NID07 00 00 C2 62 11
Module
N
o
Type: SOU S+ 2x4A
Key OK=deactivate
Menu 5.2:
<ok>
Selection of a module address with
<ok>: Activation of module address
and search for further modules.
NID07 00 00 C2 62 11
Module
N
o
Type: SOU S+ 2x4A
Key OK=activate
Select line 2 or 4 or the input fields in
line 2 with
Successive selection of module
and circuit with
Changing the circuit name:
– Select line 4 with
– Select the input point with
– All the possible alphanumeric
characters are displayed cycli-
cally with the cursor keys
.
– Once a name has been fully
entered, confirm the entry with
<ok>. The remaining characters
after the current cursor position
are cleared.
Finish and return to Menu 5 with
<Menu>
Notes:
This menu can be used to assign/edit
circuit names without affecting the con-
figuration.
The procedure is necessary, for example
when the system is first commissioned or
after adding modules.
Circuit names are stored on the memory
card and displayed in the graphic display
menus as operator help. Text assignments
cannot be made with the CU S
+
if a memory
card is not inserted!
Otherwise, refer to menu option 4.2.
Menu 5.3:
<ok>
Text assignments
Module8
circuit :
2
Type: SU S+ 2x6A
Circuit name
Deactivate module
Search ext. modules
Text assignment
DLS/TLS-Assignment
Deactivate module
Search ext. modules
Text assignment
DLS/TLS-Assignment
Deactivate module
Search ext. modules
Text assignment
DLS/TLS-Assignment
Summary of Contents for Ceag AT-S+ C0
Page 76: ...400 71 860 177 XXX 07 12 WK...