CEAG Notlichtsysteme GmbH
70
Appendix
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
Appendix B:
VDE requirements for telecommunication contacts and buzzers
Default setting AT-S
+
Notes / Comments
Designation
Relay 1
C0/14/12
Relay 2
C0/24/22
Relay 3
C0/34/32
Relay 4
C1/44
Relay 5
C1/54
Buzzer
Ready for operation
X
Fest konfiguriert zur Ansteuerung einer technischen Schrankbelüftung.
Defaulteinstellung >40°C ON < 35°C OFF
.
Ready for operation means:
AT-S
+
not blocked and external
power source for safety purpo-
ses ready for operation when
detected via Z1 - Z4.
Mains failure S3/S4
X
Mains failure S3/S4 means:
Mains failure via S3 / S4 current
loop detected.
Mains failure
DLS/3PH
X
Mains failure DLS/3Ph means:
Mains failure via external bus
phase monitor detected.
Ext. source error
X
Ext. source error means: power
source for safety services defec-
tive (detected via Z1 - Z4).
Circuit fault
X
Circuit fault means:
•
Circuit fuse defective
•
Circuit overload
Luminaire fault
X
Luminaire fault means: Faulty
luminaire
Device fault
X
Device fault means:
•
transmission fault
•
substation fault
•
memory card fault
•
fault detected via Z1-Z4 for
external monitor devices
ISO error
X
ISO error means: external isola-
tion error detected via Z1 - Z 4.
Ext. source active
X
Ext. source active means: power
source for safety services swit-
ched on (detected via Z1 - Z4).
Function test
X
(perma-
nently
configured)
Function test means: test for
testing the luminaires. The
contact switches leading (freely
configurable from 0 s to 500ms).
Invert contact
X
Invert contact means: relay
coil is not ernergized for the
programmed options
X =
active
, i.e. contacts C0/14, C0/24, C0/34, C1/44 and C1/54 are closed