CEAG Notlichtsysteme GmbH
17
Construction and Function
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
Configuration
At the front of the device
using keys and graphic gisplay. There are considerable possiblities for userdefined settings via a menu
controlled parameterisation (compare chapter 9).
Via data exchange
via memory card, e. g. for a transfer of the settings between similar cabinets.
External configuration of the control module is possible with
– a usual personal computer (PC) and
– CEAG-software for the system AT-S
+
.
Communication and control
Data exchange
with installed S
+
components and V-CG-S-compatible ballasts (using the cables of the final circuits)
RS485 bus
suitable for central or decentral configuration of the SU S
+
and SOU S
+
circuit modules. Up to max. 40 circuit
modules can thus be assigned to the CU S
+
control unit. The RS 485 bus also enables data exchange with
external assemblies (DLS/3PH-bus-modules or TLS-bus-modules, RS485 port on the control module, up to 25
devices).
External CG-S bus port
(CEAG bus protocol) for data exchange with BMS.
Data Exchange and Storage
Internal:
with non-volatile memory in the CU S
+
control module
External:
with a memory card reader, type of the uses memory card:
SD-card / CEAG part no. 400 71 347 911 (preprogrammed)
SD-adapter
enables data exchange and saving with usual PC under the CEAG-Software for the system AT-S
+
Connections
3-tier-installation terminal with tension spring
all connections are taken out to a 3-tier-installation terminal with tension spring, see page 14: detail view and
Appendix A: „Connection Assignment“
Pluggable screw terminal block
at the device enables a simple assembly and disassembly.
Bus cables
4 x 2 x 0,8 mm, type: JY(ST)Y, Twistet Pair screended (minimum requirement).
5 signal-relay contact
over here the operating state can be recalled. For this the connection´s capacity is max. 24 V AC/DC and
0.5 A, the max. cable length is 1000m. The switching characteristic can be linked with different events.
Standard PC with