Test
Tested
Are covers and barriers in place?
Is the line feed properly connected?
Are all metallic components (e.g., support structure/substructure) properly grounded?
Has the insulation resistance* of the conductor rail system been measured according to local
technical standards, directives, and legal regulations?
Have the prescribed national electrical tests been conducted (e.g., measurement of the loop
impedance)?
* Note:
Insulation resistance test according to EN 60204-
1: 2018 ≥ 1 MΩ with measuring voltage 500 VDC. Exception for conductor
bars, conductor rails and slip rings ≥ 50 kΩ (EN 60204
-1/18.3: 2018)
For systems with heating:
Test
Tested
Has the heating wire (if present) been connected according to the project-specific documents
and the installation instructions (MV0813-0015)?
The inner and outer edges of the conductor rail were checked for burrs after the conductor rail
was shortened? Particularly where the heating wire is located, care must be taken to ensure
that there are no burrs so that the insulation of the heating wire is not damaged.
In the case of shortened rails, the chamfer was created on the stainless steel strip and the cut
surfaces deburred.
The crimping point is properly laid under the insulating profile according to the installation
instructions (MV0813-0015).
An insulation measurement between the heating wire and the conductor rail was conducted
(see MV0800-0018).
……………………………….
……………………………….
Date
Signature