Operating Instructions
Insulated Conductor Rail System
SinglePowerLine Program 0813
BAL0813-0007-EN
www.conductix.com
translated document
page 65 of 108
Fig. 88: Anchor clamp is mounted to the right and left of the hanger clamp
→
Mount each anchor clamp in the same way.
Use the QR code ("click" or "scan") to see our animation
Mounting Anchor Points
6.4.3.7
Mount heating wire (optional)
In order to increase the system availability during winter operations, conductor rail systems in outdoor systems or similar
environmental conditions are additionally provided with a heating system. Conductix-Wampfler GmbH's Conductor Rail Program
0813 is suitable for outdoor use. Therefore, heating should prevent the formation of frost on the conductor rail and the resulting loss
of contact with the current collector. The conductor rail is heated using an electrical heating conductor that is fed into the insulation
profile. It lies in the hollow cavity of the insulation profile. Each pole of a conductor rail system is heated. Terminal boxes for the
electrical connection of the heating wires are used in each case at the line feed and outfeed of a heating conductor circuit.
Among other things, the following must be observed:
→
The heating wire is supplied on a coil. An on-site suspension must be provided for the heating conductor coil.
→
A cut-out must be made in the insulating profile for the entry and exit points of the heating wire.
→
An elongated hole must be made in the insulating profile for the expansion loop of the heating wire.
→
All sharp edges must be very well deburred. Burrs damage the insulation of the heating wire.
→
After connecting the heating wire, an insulation measurement (see MV0800-0018) must be conducted.