Fault
Cause
Corrective Measures
Check the installation position at
various points in the system.
Collision with system components.
Consolidate project-specific
documents, fasten affected
components without collision,
replace damaged components.
Abrasive dust has collected at one of the more frequently
used transfer points (where the direction of travel is
reversed).
Adjust the consumer's movement
profile. Move over the end
position to slide the collected
abrasive dust out of the conductor
bar. Clean the conductor bar.
Insulating profile is not
engaged in the hanger
clamp.
Conductor rail has not been properly mounted.
Snap in the insulation profile,
check components, replace if
necessary. Install the conductor
rail as described in Section
6.4.3.3 .
Use of damaged components.
Replace damaged components.