Mount each connection point in the same way.
WARNING!
Avoid destroying the conductor rail!
→
Do not slide the conductor rails together with force.
→
Do not strike them with a hammer.
→
Observe the tightening torques and use a torque wrench.
→
Use contact grease (Order No.: 080021).
Use the QR code ("click" or "scan") to see our animation
Connecting Rails and Mounting
Line Feed
6.4.3.5
Line feed
The electrical line feeds that are used instead of the rail connectors must be mounted as close as possible to the feed cable of the
permanent installation (see Section 6.4.3.4). If the line feed is provided within a section of rail that has been cut to length, the insulating
profile must be separated there and shortened by 92.5 mm on both sides (see Section 6.4.2).
Required tools:
◼
Open-end wrench, SW17
◼
Contact grease, Order No.: 080021
◼
Steel brush
◼
Crosshead screwdriver
◼
Crimping tool
◼
Hot air dryer
Distances:
Distance between the line feed and hanger clamp: Min. 400 mm (due to temperature shift of the conductor rails).
Please refer to the project-specific documents for the exact position of a line feed.
Requirements:
The ends of the conductor rail are deburred (see Fig. 46). The line end of the line feed is stripped.
Work Steps
→
Slide the insulating cap halves (Pos. 1) of the line feed over the ends of the conductor rail (see Fig. 80).