7
– Observe all local safety regulations regarding the handling of mains-
powered electric and electronic equipment.
–
Caution! For safety reasons the Condair Dual must be installed
only in rooms provided with a floor drain. If for some reason the
Condair Dual must be installed in a location without floor drain, it
is mandatory to provide a water tub with drain or water sensors to
safely interrupt water supply in case of leakage
(e.g. option “Z402”,
see chapter 3.4 “Options”)
.
– For safe operation of the hybrid humidifier, make sure the ambient con
ditions meet the respective specifications (see chapter 7 “Technical
data/ambient conditions”).
–
Caution!
Fully demineralized water is aggressive. For this reason, perme-
ate lines and components located close to the humidification unit must
be made of
corrosion-proof steel
(minimum requirements according to
DIN 1.4301) or plastic.
– If it can be assumed that safe operation is no longer possible, the Condair
Dual must be taken out of service and secured against un intentional
operation. Safe operation may be affected in the following events:
– components of the Condair Dual are damaged.
– the Condair Dual does not work correctly.
– connectors and lines are leaking.
– components of the Condair Dual are worn or badly soiled.
– the post-evaporation elements are not correctly positioned, locked
or sealed.
– after longtime storage under unfavorable conditions.
– after transportation under unfavorable conditions.
–
Use only genuine accessories and spare parts
available from your
Condair supplier.
– The Condair Dual Hybrid Humidifier and the optional accessories
must
not be modified in any way
without the written consent of the manu-
facturer.